Technical Specification
| Operating Voltage | 24VDC / 250mA | 
|---|---|
| Number of channels | 8 Input(SPST NO/NC Switch&Button Input), 8 Outputs (Relay Output)  | 
| Number of Com. Ports | 1x RS/EIA-485 | 
| Communication protocol | Modbus RTU | 
| I/O Functionality | Input: Trigger Output: Toggle / Pulse  | 
| Isolation type | Inputs: Non-isolated Com Port: Non-isolated Outputs: Dry contact  | 
| Isolation voltage | Output contacts to system ground: 4kV (rms) | 
| Applied Voltage (VDC) to Input Channels | 24VDC (Input Channel Voltage, generated by the device) | 
| Applied Current (mA) to Input Channels | 9mA | 
| Applied Voltage to Relay Output | Max 250VAC | 
| Applied Current to Relay Output | 5A @30VDC / 10A @250VAC cosφ=1 according VDE standard)  | 
| Frequency | 50/60Hz (for Relay) | 
| Relay Type | Dry Contact SPST-NO | 
| Wiring Terminations | Insulated Wire Ferrules | 
| System expansion | Max. 3 devices in series Total 24 inputs, 24 outputs | 
Environmental Specification
| Operating Temperature | -10 ~ +60 Celsius | 
|---|---|
| Storage Temperature | -40 ~ +80 Celsius | 
| Relative humidity | – | 
Mechanical Specification
| Dimensions Height: Width: Depth:  | 84 mm 126 mm 58 mm  | 
|---|---|
| Weight | 300 g | 
| Maximum wire gauge for terminals | 28-12AWG / 2.5 mm2 | 
| Mounting | DIN or Panel mount | 
Dimensions
NIO8
    
Mounting
NIO8 modules mountable on EN50022 standard 7.5 mm x 35 mm DIN rail and panel mounting.

Caution: Both two screws must be firmly tightened to prevent unwanted movement or falling.
Ensure the module is isolated from the surface to avoid electrical leakage or shock.